First of all, such wiring is only possible using a TN electrical system. With an IT system, it is not possible to connect the charging station without the neutral wire.
For the TN system, the solution is to install a Dyn transformer (Delta to wye windings with neutral point) or to ground the N-terminal of the stations.
If this is done incorrectly or if the IT system is used, the charging station will be damaged.