For DLM to function in a standalone INCH Core charging station, an external metering device must be used:

  • INCH Core Load Guard (supports wireless connection), or

  • an external electricity meter supporting Modbus RTU communication via RS-485 wired connection, or

  • combination of both.

...

DLM configuration can be set via the INCH Core app or a central system (e.g., EMSP).

1. Enable DLM via the Dynamic load management page of the INCH Core app, or a central system if applicable.

...

To configure Load Guard for DLM to function with the charging station, refer to the INCH Core Load Guard guidelines.

Image Removed

The guidelines will be available when the INCH Core Load Guard will be launched.

External electricity meter

...

Anchor
Parameters
Parameters
To ensure successful one-way communication from the station to the meter, the station's configuration must match the following parameters of the meter:

  • Address

  • Baud rate

  • Data bits

  • Parity

  • Stop bit

 

When you select your meter type from the dropdown list in the INCH Core app, the listed parameters can be pre-configured. However, the actual values of these parameters may differ from the default values. It's important to verify and set the correct actual values accordingly.