Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

C_in_Hexagone_Small.pngImage Added

Single-phase or three-phase EV charging station for

...

Maximum charging power:

  • One-phase installation: 7.4 kW (1 × 32 A)

  • Three-phase installation: 22 kW (3 × 32 A)

...

Charging outlet type:

  • Type 2 socket

  • Type 2 tethered charging cable

...

any electric vehicle with a Type 2 charging connector (identifier C).

Electrical characteristics

Single-phase device

Input

230 V~; 1W+N+PE; 50/60 Hz; 32 Amax; 7.4 kW

Output

230 V~; 1W+N+PE; 50/60 Hz; 32 Amax; 7.4 kW

Three-phase device

Input

230/400 V~; 3W+N+PE; 50/60 Hz; 32 Amax; 22 kW

Output

230/400 V~; 3W+N+PE; 50/60 Hz; 32 Amax; 22 kW

Types of system earthing

TN, TT

Rated impulse withstand voltage (Uimp)

2500 V – OVC II (4000 V and OVC III is achieved with installed SPD)

Rated insulation voltage (Ui)

230/400 V

Rated current of each circuit (Inc)

32 A

Rated peak withstand current (Ipk)

4500 A

Rated conditional short-circuit current of assembly (Icc)

3000 A

Rated diversity factor (RDF)

  • 1 (without load control),

  • 0 to 1 (with proper setup of load control)

Device power consumption

10–15 W (highest measured value of full configuration)

...

Environmental characteristics

Ingress protection

IP56

Impact protection

...

Ingress protection: IP56 protection against dust and liquid penetration (by IEC 60529)

...

Electrical protection:

  • DC fault current sensors 6 mA (default)

  • PEN protection (UK edition)

  • Other protection installed externally upstream

...

Communication technologies allow BEMS, cloud integration and ensure communication stability.

  • Connectivity

    • Wi-Fi – for WLAN connection

    • Bluetooth & Wi-Fi – for Smartphone mobile app connection

    • Sub-1 GHz – for wireless connection with Load Guard (when used)

  • EV communication:

    • IEC 61851

    • ISO 15118 – supported by design, not available at launch

  • Local communication protocols, Smart building integration: MQTT, Modbus RTU, OCPP

  • Cloud connection: OCPP (1.6 starting version)

...

Energy meter:

  • embedded class 2 energy meter

  • can be connected with a MID compliant meter

...

Modes of charging:

  • Fast

  • Interactive

...

User identification: Smartphone app, RFID

...

User interface: LED and sound signals, press button, smartphone app

...

Material: Polycarbonate reinforced with glass fibers, TPE gasket

...

Colour: Light grey (RAL 7001)

...

Modularity – the charging station consists of three modules – enables simple and fast product installation:

  • Module 1 – Dock (Wallmount)

  • Module 2 – Output socket without shutter / Output socket with shutter / Output cable

  • Module 3 - Main unit

The charging station offers versatile connectivity options to suit various energy management systems:

...

integration with Local Energy Management System (LEMS)

...

integration with Cloud Energy Management System (CEMS)

...

IK10

Protection class

Class I equipment

Pollution degree

Pollution Degree 3

Electromagnetic compatibility (EMC)

  • EMC emissions: Class B (residential)

  • EMC immunity: Class A (other than residential)

Frequency bands and radio power

Wi-Fi

Frequency band: 2.4 GHz 

Transmitting power: up to 20.5 dBm (adjustable)

Sub-GHz 

Frequency bands: 169 MHz, 410–510 MHz, 868 MHz, or 915 MHz

Transmitting power: 14 dBm

RFID module

Frequency band: 13.56 MHz (HF)

Transmitting power: up to 8 dBm

(ISO 14443 and ISO 15693)

Other classification and characteristics

AEVCS

Assembly intended for charging stations for electric vehicles

Installation location

Indoor and Outdoor

Mounting method

Stationary equipment, Wall-mounted assembly

Location accessibility

Location with restricted access or non-restricted access

Mechanical resistance

Medium/High

Installation

Must be performed by qualified personnel

Operation

Allowed to ordinary persons

Electrical installation protection

  • Short-circuit protective device(s):
    Appropriate MCB or fuse must be part of electrical installation, installed upstream of the charging station.

  • Protection against electric shock:
    Appropriate RCD must be part of electrical installation, installed upstream of the charging station. 

Dimensions

Dimensions of assembled charging station (in mm)

image-20240229-135419.pngImage Added

H2 - to the bottom of the cable gland with a spiral

Main unit + Dock

257 × 273 × 115 (W × H1 × D)

Main unit + Output socket + Dock

257 × 401 × 115 (W × H2 × D)

Main unit + Output socket shutter + Dock

257 × 413 × 120 (W × H2 × D)

Main unit + Output Cable + Dock

257 × 387 × 115 (W × H2 × D)

Mass

Mass (assembled charging station)

3.4 kg to 7 kg
(depending on the configuration and cable length)

Temperature

Operational

-25 °C to +85 °C

Ambiental

-25 °C to +50 °C

Storage

-30 °C to +85 °C